The UNI-T UT595 combines insulation resistance, continuity, line and loop impedance, RCD, phase sequence and voltage testing in one portable instrument. Its automatic RCD test sequence and comprehensive test modes make it suitable for electrical installation inspection, commissioning and maintenance.
Key Features
- Insulation resistance testing at selectable 250V, 500V and 1000V DC test voltages, with measurement ranges up to 1000MΩ.
- Low-resistance continuity testing with over 200mA test current for checking protective conductors and bonding connections.
- Line, loop and non-trip loop impedance testing, with prospective fault and short-circuit current measurement up to 26kA.
- Automatic RCD testing at 10mA, 30mA, 100mA, 300mA and 500mA, including ×1/2, ×1, ×2, ×5, ramp and countdown modes.
- Phase sequence, missing-phase and voltage testing, supported by a 9999-count backlit display, data storage and connection-status indication.
Product Specifications
| Insulation Resistance |
| Test Voltages |
250V / 500V / 1000V DC, ±10% |
| Range at 250V |
0.05MΩ–250MΩ |
| Range at 500V |
0.05MΩ–500MΩ |
| Range at 1000V |
0.05MΩ–1000MΩ |
| Accuracy |
±(5% + 5 digits) |
| Short-Circuit Current |
Less than 2mA |
| Continuity and Impedance |
| Low-Resistance Continuity Range |
0.00Ω–199Ω |
| Continuity Accuracy |
±(2% + 5 digits) |
| Continuity Test Current |
Greater than 200mA at 0.00Ω–2Ω |
| Line Impedance Range |
0.01Ω–2000Ω |
| Loop Impedance Range |
0.01Ω–2000Ω |
| Non-Trip Loop Impedance Range |
1.00Ω–2000Ω |
| Line and Loop Test Current |
20A |
| Non-Trip Loop Test Current |
15mA |
| PFC / PSC Range |
0–26kA |
| RCD Testing |
| Operating Voltage |
195V–253V AC, 45Hz–65Hz |
| Selectable Test Currents |
10mA / 30mA / 100mA / 300mA / 500mA, ±10% |
| ×1/2 IΔn Trip-Time Range |
0–2000ms |
| ×1 IΔn Trip-Time Range |
0–300ms; 0–500ms in countdown mode |
| ×2 IΔn Trip-Time Range |
0–150ms; 0–200ms in countdown mode |
| ×5 IΔn Trip-Time Range |
0–40ms |
| RCD Phase Angle |
0° / 180° |
| RCD Test Modes |
Automatic sequence, full-wave, half-wave, ramp and 30-second countdown |
| Voltage and Phase Sequence |
| AC Voltage Range |
0–440V |
| AC Voltage Accuracy |
±(5% + 2 digits) |
| Voltage Frequency Response |
45Hz–60Hz |
| Phase Sequence Operating Range |
100V–440V AC, 45Hz–65Hz |
| Phase Sequence Indication |
L1→L2→L3 forward; L1→L3→L2 reverse |
| General |
| Display |
9999-count LCD with analogue bar graph and white backlight |
| Additional Functions |
Data storage, test lock, connection check, low-battery indication and automatic power-off |
| Power Supply |
6 × 1.5V AA batteries |
| LCD Size |
125 × 37mm |
| Product Dimensions |
210 × 175 × 90mm |
| Net Weight |
1000g |
| Certification |
CE |
Applications
- Inspection and commissioning of domestic, commercial and industrial electrical installations.
- Testing insulation integrity, protective conductors and bonding connections.
- Verification of line impedance, loop impedance, prospective fault current and RCD operation.
- Electrical maintenance, fault finding, phase sequence checks and safety inspections.
Included Components
- UNI-T UT595 multifunction electrical installation tester
- Red, green and black test leads
- Special mains test lead
- Remote-control test lead
- 6 × 1.5V AA batteries
- User manual
- Warranty card
- Tool case